Lithium iron phosphate (LiFePO4) batteries are easy to live with and hard to read. A lead-acid battery tells you a lot through its voltage; a LiFePO4 pack sits at almost the same voltage from nearly full to nearly empty. This guide shows the chart, explains why its middle is flat, and says when you can trust a voltmeter.
You can try every number below in the free LiFePO4 voltage chart and state of charge calculator, which runs in the browser and shows how far off an estimate can be.
The resting chart
These are per-cell resting voltages, measured after a battery has sat for a few hours with no charge and no load. Renogy and Jackery publish the same values; a pack’s voltage is the cell value times the number of cells in series.
| State of charge | Per cell | 12 V (4S) | 24 V (8S) | 48 V (16S) |
|---|---|---|---|---|
| 100 %, rested | 3.40 V | 13.60 V | 27.20 V | 54.40 V |
| 90 % | 3.35 V | 13.40 V | 26.80 V | 53.60 V |
| 80 % | 3.32 V | 13.28 V | 26.56 V | 53.12 V |
| 70 % | 3.30 V | 13.20 V | 26.40 V | 52.80 V |
| 60 % | 3.27 V | 13.08 V | 26.16 V | 52.32 V |
| 50 % | 3.26 V | 13.04 V | 26.08 V | 52.16 V |
| 40 % | 3.25 V | 13.00 V | 26.00 V | 52.00 V |
| 30 % | 3.22 V | 12.88 V | 25.76 V | 51.52 V |
| 20 % | 3.20 V | 12.80 V | 25.60 V | 51.20 V |
| 10 % | 3.00 V | 12.00 V | 24.00 V | 48.00 V |
| 0 % | 2.50 V | 10.00 V | 20.00 V | 40.00 V |
While charging, a cell can read up to 3.65 V (14.6 V for a 12 V pack), the usual charge limit; it settles back toward 3.40 V once charging stops. Separate pages show the 12 V chart, the 24 V chart and the 48 V chart with charging setpoints for each size.
Why the middle is flat
Look at the rows from 90 % down to 20 %: a resting cell moves from 3.35 V to 3.20 V. Seventy percent of the battery’s charge lives inside 0.15 V per cell, or 0.6 V across a 12 V pack.
That has a practical consequence. Between 70 % and 80 % the chart moves only 0.02 V per cell, so a meter reading that is off by 0.01 V per cell moves the estimate by about five points. A cheap multimeter, a long cable or a reading taken a little too soon after charging can easily be off by that much. The calculator shows this sensitivity for every reading, so you can see when an estimate is solid and when it is a guess.
The curve turns steep only at the ends. Above about 3.35 V the cell is nearly full; below about 3.20 V it drops fast toward empty. Those are the two places where voltage tells you something clearly.
How to get a usable reading
- Let it rest. Disconnect charge sources and loads, wait a few hours, then measure. Charging adds to the voltage and a load subtracts from it.
- Measure at the battery terminals, not at the far end of a cable, where current through the wire changes the reading.
- Compare like with like. If you cannot rest the battery, compare readings taken the same way at the same time of day, and watch the trend rather than one number.
- Mind the temperature. Cold cells read lower; every maker’s cells differ slightly. Treat the chart as a range.
What a BMS does better
A smart battery management system (BMS) measures the current going in and out and counts amp-hours. Its state of charge does not depend on the flat part of the curve, so it holds up while you are charging, driving or cooking. A shunt-based battery monitor does the same for the whole bank.
Most smart BMS boards report that number over Bluetooth, together with each cell’s voltage. Amphour is an iPhone and iPad app that reads JBD and Xiaoxiang smart BMS (tested on real hardware), Victron battery monitors and chargers with Instant Readout, and Daly BMS (experimental). It shows the state of charge the BMS counts, every cell beside it, keeps the history on your device and warns you before a cell drifts out of range. It only reads; it never changes BMS settings.
Before you change anything
Charge voltages, low-voltage cutoffs and wiring belong to your battery maker’s datasheet and to a qualified electrician. Use the chart to understand a reading, not to set a charger.